Create a Configuration Example¶
The following sections describe the first steps for the visual representation of a machine value, including useful information on configuring and establishing a connection with a telematics unit.
The example below describes the steps for displaying the engine speed, SPN 190 of PGN 61444 with priority 0x6 and source address 0x00 according to the J1939-71 standard.
The description assumes that a 29-bit CAN message with the CAN identifier 0x18F00400 is present on the connected CAN bus and transmits the current engine speed.
Note
If an Remote Service Tool configuration with the corresponding settings already exists, continue directly with Connect to a Device and Visualize Data.
- Make sure that the latest version of Remote Service Tool from the Download Center is installed on your PC.
- Start Remote Service Tool.
✓ The software starts with a blank project.
- Make sure that Project > Edit mode enabled (
Ctrl+E) is active in the menu.

- Right-click in the Main tab.
- Click Add element.
- Select Gauge from the available elements.

✓ The Gauge element is added to the main tab of your Remote Service Tool configuration.
- Right-click the new gauge element and click Configure….

✓ The configuration dialog for the gauge element opens.
- Click Source.

- Configure the gauge element according to the following table.

| # | Item | Setting |
|---|---|---|
| 1 | Active | Enabled. |
| 2 | Source name | Enter Engine Speed. |
| 3 | CAN channel | Select 0 for CAN1 (1 = CAN2). |
| 4 | Message type | Select 29 bit CAN message. |
| 5 | CAN identifier | Enter 18F00400 for PGN 61444 with priority 0x6 and source address 0x00. |
| 6 | Data type | Uint16 |
| 7 | Byte order | LSB first |
| 8 | First byte | 4 |
| 9 | Multiplier | 0,125 |
| 10 | Offset | 0 |
- Click Gauge within the Element configuration dialog.
-
Enter a Maximum value of
10000.
Figure 6: Gauge maximum value -
Click OK.
- Click the filter settings icon
. -
Select Auto filter (global).

Figure 7: Filter configuration Note
Enabling Auto filter (global) is typically the last step once the widget configuration is complete. Make sure it stays enabled once the Remote Service Tool configuration is finished, so the required filter masks are calculated.
-
Press
Ctrl+Eto disable Project > Edit mode enabled.✓ The gauge element and the required filter are configured.
Tip
If the correct CAN identifier is unknown, add a CAN Monitor element and create a CAN trace to determine the priority and source address for the PGN, see Record a CAN Trace with CAN Monitor.
-
Click Save (
Ctrl+S) to save the configuration as a.dbsfile for further tests.